PARTS & ACCESSORIES
Product Sheet - Model 7505 Product Description The Beckett GeniSys® Advanced Burner Control is a 120 Vac primary safety control for residential and light commercial oil burners used in boiler, furnace, and water heater applications. The GeniSys is used with a suitable cad cell flame sensor to control the oil burner motor, igniter, and optional solenoid valve. It has 24 Vac thermostat terminals (if applicable) compatible with both mechanical and many power stealing thermostats. It can provide interrupted or intermittent duty ignition, and it has a 15-second lockout time.
Features & Benefits • Improved water resistance • New protective overlay label • Thermostat and boiler control compatible • Customizable pre-time and post-time • Three status lights for system monitoring and diagnostics • Welded relay protection with redundant motor relays • Limited reset and limited recycle • Sleek, modern design • Technician Pump Prime mode • 5- Year Warranty
Add a GeniSys® Contractor Tool to fully utilize the features of the GeniSys advanced burner control. The GeniSys Contractor Tool (Pt. No. 52082U) allows a technician to monitor and program the primary control variables. The display shows current burner status, control timings, and burner cycle history. The display’s programming mode allows a technician to customize both the pre-time and post-time settings and a lockout service message. • 32 character backlit alphanumeric display • Sealed push-button keypad • Low voltage operation • Continuous real-time cycle monitoring • Continuous cad cell resistance reading • Continuous AC line voltage read-out • Real-time error notification • Customizable pre-time (valve-on delay) & post-time (motor off delay) • 15 cycle history monitoring • 18-Month Warranty • Customizable lockout service message
To learn more, see www.beckettcorp.com or ask for literature #61687.
PARTS & ACCESSORIES
Product Sheet - Model 7505 Cross-Reference Chart Beckett GeniSys Control Part No.
Lockout Time
Valve-on delay time2
Motor-off delay time2
Replaces Honeywell:
Replaces Carlin:
7505A 0000
15 sec
-
-
R7184A, R8184G, R7284G
48245, 40200 42230, 502001
7505B 1500
15 sec
15 sec
-
R7184B, R7284B
-
7505P 1515
15 sec
15 sec
15 sec
R7184P, R7184U1, R7284P, R7284U1
602001, 702001
7505P 1530
15 sec
15 sec
30 sec
R7184P, R7184U1, R7284P, R7284U1
602001, 702001
7505P 152M
15 sec
15 sec
2 min
R7184P, R7184U R7284P, R7284U
602001, 702001
1,
1
1) Beckett snap-in alarm module required for direct replacement of the control. 2) Valve-on delay and motor-off delay timings on all models are programmable with Beckett Contractor’s Tool. Other factory set timings are available. Contact Beckett for alternate timings.
Electrical Ratings Inputs
Application Ratings
Voltage: 102 to 132 Vac Current: 150 mA plus burner motor, igniter, and valve loads Frequency: 60 Hz
Oil Burner Input: < 20gph Control Programming: UL372 Group 2
Outputs Motor: 120 Vac, 10 full load amps (FLA*), 60 locked rotor amps (LRA) Note – Reduce motor FLA rating by igniter current Igniter: 120 Vac, 3 A @ 0.7 PF min Solenoid Valve: 120 Vac, 1 A @ 0.7 PF min Thermostat Anticipator Current: 0.1 A Thermostat Voltage: 24 Vac
Environmental Ratings Storage & Operating Ambient Temp.: -40°F to +150°F (-40°C to +65°C) Moisture: 5 to 95% RH, non-condensing and non-crystallizing
Approvals
Underwriters Laboratory Recognition per UL372 and UL1998, and CSA C22.2 No. 199
Operation Sequence of Operation
2
9 Standby
Valve-on delay
3
5
8
Motor-off delay
6
Trial for ignition
4
Pump prime
Lockout
Disable Function
Ignition carryover Run
If the control locks out three times without a satisfied call for heat or fails the motor relay check, the Lockout becomes restricted in order to prevent repetitious resetting by the homeowner. To reset, hold the button down for 15 seconds until the red light turns off and the yellow LED turns on.
7
Recycle
Priming The Pump 1. Initiate a call for heat. 2. When the burner starts, press and hold the reset button for 15 seconds until the yellow light turns on. 3. Release the button. The yellow light will turn off and the burner will start again. 4. At burner start up, click the reset button while the igniter is still on to enter Pump Prime mode. The yellow light will turn on. 5. Bleed the pump until all froth and bubbles are purged. 6. If necessary, repeat steps 4 and 5 until the pump is fully primed and the oil is free of bubbles. 7. When finished, hold the reset button or remove the call for heat to exit Pump Prime mode and return to Standby.
Any time the burner is running, press and hold the reset button to disable the burner. The burner will remain off as long as the button is held.
Cad Cell Resistance Measurement If the Beckett 7505 control is equipped with the GeniSys Contractor Tool, part 52082U, the cad cell resistance can be selected and read on the LCD screen. If this is not available, the cad cell leads can be unplugged from the control and the resistance measured with a meter in the conventional way. Conduct these tests with flame present. Flame Detection Range Normal = 0 to 1600 ohms Limited = 1600 ohms to lockout
Form No. 61658 R12, Printed in the USA 10/16
1
Resetting From Restricted Lockout
Product Sheet - Model 7505 Product Description The Beckett GeniSys® Advanced Burner Control is a 120 Vac primary safety control for residential and light commercial oil burners used in boiler, furnace, and water heater applications. The GeniSys is used with a suitable cad cell flame sensor to control the oil burner motor, igniter, and optional solenoid valve. It has 24 Vac thermostat terminals (if applicable) compatible with both mechanical and many power stealing thermostats. It can provide interrupted or intermittent duty ignition, and it has a 15-second lockout time.
Features & Benefits • Improved water resistance • New protective overlay label • Thermostat and boiler control compatible • Customizable pre-time and post-time • Three status lights for system monitoring and diagnostics • Welded relay protection with redundant motor relays • Limited reset and limited recycle • Sleek, modern design • Technician Pump Prime mode • 5- Year Warranty
Add a GeniSys® Contractor Tool to fully utilize the features of the GeniSys advanced burner control. The GeniSys Contractor Tool (Pt. No. 52082U) allows a technician to monitor and program the primary control variables. The display shows current burner status, control timings, and burner cycle history. The display’s programming mode allows a technician to customize both the pre-time and post-time settings and a lockout service message. • 32 character backlit alphanumeric display • Sealed push-button keypad • Low voltage operation • Continuous real-time cycle monitoring • Continuous cad cell resistance reading • Continuous AC line voltage read-out • Real-time error notification • Customizable pre-time (valve-on delay) & post-time (motor off delay) • 15 cycle history monitoring • 18-Month Warranty • Customizable lockout service message
To learn more, see www.beckettcorp.com or ask for literature #61687.
PARTS & ACCESSORIES
Product Sheet - Model 7505 Cross-Reference Chart Beckett GeniSys Control Part No.
Lockout Time
Valve-on delay time2
Motor-off delay time2
Replaces Honeywell:
Replaces Carlin:
7505A 0000
15 sec
-
-
R7184A, R8184G, R7284G
48245, 40200 42230, 502001
7505B 1500
15 sec
15 sec
-
R7184B, R7284B
-
7505P 1515
15 sec
15 sec
15 sec
R7184P, R7184U1, R7284P, R7284U1
602001, 702001
7505P 1530
15 sec
15 sec
30 sec
R7184P, R7184U1, R7284P, R7284U1
602001, 702001
7505P 152M
15 sec
15 sec
2 min
R7184P, R7184U R7284P, R7284U
602001, 702001
1,
1
1) Beckett snap-in alarm module required for direct replacement of the control. 2) Valve-on delay and motor-off delay timings on all models are programmable with Beckett Contractor’s Tool. Other factory set timings are available. Contact Beckett for alternate timings.
Electrical Ratings Inputs
Application Ratings
Voltage: 102 to 132 Vac Current: 150 mA plus burner motor, igniter, and valve loads Frequency: 60 Hz
Oil Burner Input: < 20gph Control Programming: UL372 Group 2
Outputs Motor: 120 Vac, 10 full load amps (FLA*), 60 locked rotor amps (LRA) Note – Reduce motor FLA rating by igniter current Igniter: 120 Vac, 3 A @ 0.7 PF min Solenoid Valve: 120 Vac, 1 A @ 0.7 PF min Thermostat Anticipator Current: 0.1 A Thermostat Voltage: 24 Vac
Environmental Ratings Storage & Operating Ambient Temp.: -40°F to +150°F (-40°C to +65°C) Moisture: 5 to 95% RH, non-condensing and non-crystallizing
Approvals
Underwriters Laboratory Recognition per UL372 and UL1998, and CSA C22.2 No. 199
Operation Sequence of Operation
2
9 Standby
Valve-on delay
3
5
8
Motor-off delay
6
Trial for ignition
4
Pump prime
Lockout
Disable Function
Ignition carryover Run
If the control locks out three times without a satisfied call for heat or fails the motor relay check, the Lockout becomes restricted in order to prevent repetitious resetting by the homeowner. To reset, hold the button down for 15 seconds until the red light turns off and the yellow LED turns on.
7
Recycle
Priming The Pump 1. Initiate a call for heat. 2. When the burner starts, press and hold the reset button for 15 seconds until the yellow light turns on. 3. Release the button. The yellow light will turn off and the burner will start again. 4. At burner start up, click the reset button while the igniter is still on to enter Pump Prime mode. The yellow light will turn on. 5. Bleed the pump until all froth and bubbles are purged. 6. If necessary, repeat steps 4 and 5 until the pump is fully primed and the oil is free of bubbles. 7. When finished, hold the reset button or remove the call for heat to exit Pump Prime mode and return to Standby.
Any time the burner is running, press and hold the reset button to disable the burner. The burner will remain off as long as the button is held.
Cad Cell Resistance Measurement If the Beckett 7505 control is equipped with the GeniSys Contractor Tool, part 52082U, the cad cell resistance can be selected and read on the LCD screen. If this is not available, the cad cell leads can be unplugged from the control and the resistance measured with a meter in the conventional way. Conduct these tests with flame present. Flame Detection Range Normal = 0 to 1600 ohms Limited = 1600 ohms to lockout
Form No. 61658 R12, Printed in the USA 10/16
1
Resetting From Restricted Lockout
Since 1948 Beckett has been a recognized leader in designing innovative and reliable pumps for water gardening, industrial, and OEM markets. While manufacturing pumps remains the core of our business, over the years we have transformed to reach broader consumer audiences.
PARTS & ACCESSORIES
Cross-Reference Guide - Model 7505 Features & Benefits • Thermostat and boiler control compatible • Programmable valve-on delay and motor-off delay • Three status lights for system monitoring and diagnostics • Welded relay protection with redundant motor relays • Limited reset and limited recycle • Sleek, modern design • Technician Pump Prime mode • 5-Year Warranty • Two communication ports for adding alarm contacts, programming display, and/or future wireless communications
Manufacturer
Model
Lockout
Pre*
Post**
Beckett GeniSys Recommended Replacement
Carlin
40200-02
15
0
0
7505A-0000
Carlin
42230-02
30
0
0
7505A-0000
45
0
0
7505A-0000
Carlin
48245 (Intermittent Ignition)
7505A-0000
Carlin
50200-02
15
0
0
Carlin
60200-02
15
10
10
Honeywell
R7184A1000 R7184A1026 R7184A1075
15
0
0
Honeywell
R7184A1018 R7184A1034
Honeywell
R7184A1042
45
0
0
7505A-0000
Honeywell
R7184B1016 R7184B1024 R7184B1032
15
15
0
7505B-1500
Honeywell
R7184P1080
15
15
15
7505P-1515
Honeywell
R7184P1056 R7184P1064
15
15
selectable
7505P-1515
Honeywell
R7184P1049 R7184P1072 R7184U1004
15
0/15
selectable
Honeywell
R7184U1012
30
0/15
selectable
(+ 52040 Alarm Module)
7505P-1515 (+ 52040 Alarm Module)
7505A-0000 7505A-0000
7505P-152M (+ 52040 Alarm Module)
7505P-152M (+ 52040 Alarm Module)
Continued on back ►
PARTS & ACCESSORIES
Cross-Reference Guide - Model 7505 ◄ Continued from front Manufacturer
Model
Lockout
Pre*
Post**
Honeywell
R7184U1020
45
0/15
selectable
15, 30, or 45
0
0
7505A-0000
15 or 45
15
4 min.
7505P-152M
45
0
0
Honeywell Honeywell Honeywell
R8184G (Intermittent Ignition)
R8184P (Intermittent Ignition)
R8184M (Intermittent Ignition)
Beckett GeniSys Recommended Replacement 7505P-152M (+ 52040 Alarm Module)
7505A-0000 (+ 51950 A/C Ready Kit)
White-Rogers
668-364 668-601
15
0
0
7505A-0000
White-Rogers
668-264 668-501
30
0
0
7505A-0000
White-Rogers
668-401 668-430
45
0
0
7505A-0000
White-Rogers
668-451
45
0
0
7505A-0000 (+ 51950 A/C Ready Kit)
All Beckett recommended controls are interrupted duty ignition controls with a 15 second safety lockout, limited recycle, limited reset, communication o o ports, diagnostic LEDs and ambient temperature range from -40 F to +150 F. For replacement information concerning controls not listed above, contact your Beckett sales representative or call our technical service department at: 1-800-OIL BURN (1-800-645-2876) 8AM to 5PM EST, Monday thru Friday. * The pre (valve on delay) timing on all GeniSys controls can be reprogrammed by the GeniSys display.
◄ GeniSys Control shown with 52067 GeniSys Display and 52040 Alarm module
USA: R.W. Beckett Corporation • ph: (800)645-2876 • fax: (440)327-1064
| Canada: R.W. Beckett Canada Ltd. • ph: (800)665-6972 • fax: (519)763-5656
www.beckettcorp.com
Form No. 61492 R05, Printed in the USA 08/10
** The post (motor off delay) timing on all GeniSys controls can be reprogrammed by the GeniSys display.
Cross-Reference Guide - Model 7505 Features & Benefits • Thermostat and boiler control compatible • Programmable valve-on delay and motor-off delay • Three status lights for system monitoring and diagnostics • Welded relay protection with redundant motor relays • Limited reset and limited recycle • Sleek, modern design • Technician Pump Prime mode • 5-Year Warranty • Two communication ports for adding alarm contacts, programming display, and/or future wireless communications
Manufacturer
Model
Lockout
Pre*
Post**
Beckett GeniSys Recommended Replacement
Carlin
40200-02
15
0
0
7505A-0000
Carlin
42230-02
30
0
0
7505A-0000
45
0
0
7505A-0000
Carlin
48245 (Intermittent Ignition)
7505A-0000
Carlin
50200-02
15
0
0
Carlin
60200-02
15
10
10
Honeywell
R7184A1000 R7184A1026 R7184A1075
15
0
0
Honeywell
R7184A1018 R7184A1034
Honeywell
R7184A1042
45
0
0
7505A-0000
Honeywell
R7184B1016 R7184B1024 R7184B1032
15
15
0
7505B-1500
Honeywell
R7184P1080
15
15
15
7505P-1515
Honeywell
R7184P1056 R7184P1064
15
15
selectable
7505P-1515
Honeywell
R7184P1049 R7184P1072 R7184U1004
15
0/15
selectable
Honeywell
R7184U1012
30
0/15
selectable
(+ 52040 Alarm Module)
7505P-1515 (+ 52040 Alarm Module)
7505A-0000 7505A-0000
7505P-152M (+ 52040 Alarm Module)
7505P-152M (+ 52040 Alarm Module)
Continued on back ►
PARTS & ACCESSORIES
Cross-Reference Guide - Model 7505 ◄ Continued from front Manufacturer
Model
Lockout
Pre*
Post**
Honeywell
R7184U1020
45
0/15
selectable
15, 30, or 45
0
0
7505A-0000
15 or 45
15
4 min.
7505P-152M
45
0
0
Honeywell Honeywell Honeywell
R8184G (Intermittent Ignition)
R8184P (Intermittent Ignition)
R8184M (Intermittent Ignition)
Beckett GeniSys Recommended Replacement 7505P-152M (+ 52040 Alarm Module)
7505A-0000 (+ 51950 A/C Ready Kit)
White-Rogers
668-364 668-601
15
0
0
7505A-0000
White-Rogers
668-264 668-501
30
0
0
7505A-0000
White-Rogers
668-401 668-430
45
0
0
7505A-0000
White-Rogers
668-451
45
0
0
7505A-0000 (+ 51950 A/C Ready Kit)
All Beckett recommended controls are interrupted duty ignition controls with a 15 second safety lockout, limited recycle, limited reset, communication o o ports, diagnostic LEDs and ambient temperature range from -40 F to +150 F. For replacement information concerning controls not listed above, contact your Beckett sales representative or call our technical service department at: 1-800-OIL BURN (1-800-645-2876) 8AM to 5PM EST, Monday thru Friday. * The pre (valve on delay) timing on all GeniSys controls can be reprogrammed by the GeniSys display.
◄ GeniSys Control shown with 52067 GeniSys Display and 52040 Alarm module
USA: R.W. Beckett Corporation • ph: (800)645-2876 • fax: (440)327-1064
| Canada: R.W. Beckett Canada Ltd. • ph: (800)665-6972 • fax: (519)763-5656
www.beckettcorp.com
Form No. 61492 R05, Printed in the USA 08/10
** The post (motor off delay) timing on all GeniSys controls can be reprogrammed by the GeniSys display.